Model | APO 1000 | APO 2000 | APO 3000 | ||
Capacity | 1kVA/900W | 2kVA/1800W | 3kVA/2700W | ||
Input | |||||
Rated voltage | 208/220/230/240V AC | ||||
Voltage range | 110 to 176V AC (linear derating between 50% and 100% load) 176 to 280V AC (no derating) 280 to 300V AC (derating 50%) |
||||
Frequency | 40 to 70Hz (auto-sense) | ||||
Power factor | ≥ 0.99 | ||||
Bypass voltage range | -25 to +15% (settable) | ||||
Output | |||||
Voltage | 208/220/230/240V AC (settable) | ||||
Voltage regulation | ± 1% | ||||
Frequency | Mains mode: synchronized with utility, 45 to 55Hz or 55 to 65 Hz (synchronized range) Battery mode: 50/60 ±0.1Hz |
||||
Waveform | Sinusoidal | ||||
Crest factor | 3:1 | ||||
Harmonic distortion | ≤ 2% with linear load, ≤5% with non-linear load | ||||
Transfer time | Mains mode to battery mode: 0ms Inverter mode to bypass mode: 4ms (typical) |
||||
Overload capability | 105 to 125%: transfer to bypass in 1 min 125 to 150%: transfer to bypass in 30S > 150%: transfer to bypass in 300ms |
||||
Efficiency | |||||
Mains mode | ≥ 90% | ≥ 91% | ≥ 92% | ||
Battery mode | ≥ 85% | ≥ 86% | ≥ 87% | ||
ECO mode | ≥ 95% | ≥ 96% | ≥ 97% | ||
Batteries | |||||
Inbuilt battery/DC voltage | Standard model | 12V/9Ah × 2 (24V) | 12V/9Ah × 4 (48V) | 12V/9Ah × 6 (72V) | |
12V/7Ah × 3 (36V) | 12V/7Ah × 6 (72V) | 12V/7Ah × 8 (96V) | |||
Extensible model | 36V | 72V | 96V | ||
Charging current (max) | Standard model: 1 A, extensible model: 6 A | ||||
Recharge time | Standard model: 90% capacity restored in 3 hours Extensible model: depend on capacity of battery |
||||
Communications | |||||
RS232 (standard)/ USB (optional) | Supports Windows 98/2000/2003/XP/Vista/2008/Windows 7/8/10 | ||||
SNMP (optional) | Power management from SNMP manager and web browser | ||||
Others | |||||
Protections | Overload, surge, short circuit, battery low voltage, battery overcharge, over-temperature | ||||
Operating temperature | 0 to 40℃ | ||||
Relative Humidity | 0 to 90% (non-condensing) | ||||
Noise level | ≤ 50dB (1m) | ||||
Dimensions (W×D×H) (mm) | Standard model | 144×336×214 (24V) | 191×418×335 | 191×418×335 (72V) | |
144×414×214 (36V) | 191×464×335 (96V) | ||||
Extensible model | 144×336×214 | 191×418×335 | |||
Packaged dimensions (W×D×H) | Standard model | 232×417×318 (24V) | 318×533×471 | 318×533×471 (72V) | |
232×492×318 (36V) | 318×573×471 (96V) | ||||
Extensible model | 232×417×318 | 318×533×471 | |||
Net weight/gross weight (Kg) | Standard model | 9.5/10.5 (24V) | 18/19.5 (48V) | 27.2/29 (72V) | |
13/14.2 (36V) | 25.7/27.4 (72V) | 32/34 (96V) | |||
Extensible model | 6/7 | 10.5/12 | 11/12.5 |